Microwave Type Level Switch MWS Series

This non-contact type microwave level switch is suitable for detecting dust, coal, gravels, granules etc.

Catalog Download

Features

  • Detection is not easily affected by contamination, adhesion, and scale on the detection surface.
  • Reduction in size and weight has been realized by adopting new model of 24 GHz transmitter and receiver.
  • Paper and dust, which are difficult to detect through other methods, can be surely detected.
  • Remote amplifier model is available for the tank with vibration.

Operating Principles

When microwaves between the transmitter and receiver is blocked by material, the microwaves are reflected and absorbed. Then the receiver cannot receive microwaves and it outputs contact.
ModelMWS2-24TN/RN
Power Source AC105V/210V ±10% 50/60Hz,
option DC24V
Frequengcy 24GHz
Operating Distance Max.35m
Contact Capacity AC250V 5A Max
ON Delay Max.10seconds (variable)
OFF Delay Max.10seconds (variable)
Power Consumption 4VA (Transmitter)/5VA (Receiver)
Ambient Temperature Body:-20℃~+80℃(heat-resistant specification available)
Amplifier:-20℃~+60℃ Neither condensed nor frozen
Color Gold
Process Connection G1B or JIS5K 50A
Enclosure Rating IP67

Product Lineup

In addition to the above, various specifications are available.
For more information, see respective catalogs or contact us by phone or mail.

  • MWS2-24TN/RN

    Standard Flange Type

    MWS2-24TN/RN

    Standard Flange Type

    • Measuring distance up to 35m.
    • Boss length shorter model is available.
    • Flange material AC (JIS5K65A) is available.
    • Wetted part material stainless steel is available.
  • MWS2-24TN/RN-S

    Screwed Joint Type

    MWS2-24TN/RN-S

    Screwed Joint Type

    • Process connection G1B.
    • Measuring distance 2m Max.
  • MWS2-24TN-RN-R

    Remote Amplifier Type

    MWS2-24TN-RN-R

    Remote Amplifier Type

    • Suitable for the tank with vibration.
    • Suitable for too high or too narrow applications to reach for adjustment.