Diaphragm Type Level Switch KF-500 Series
No power source is required!
Viscous and high temperature liquid is detectable!
Features
- Simply designed moving part ensures its stable operation.
- Liquid in a tank contacts the detecting pipe but does not touch the main body of the switch.
- Highly viscous and cohesive liquid as well as high-temperature liquid, which is difficult for the float switch to detect, can be detected.
Operating Principles
As the water level in the tank rises, the internal pressure of the detecting pipe increases and the diaphragm pushes the micro switch to make contact output. As the water level falls and the internal pressure of the detecting pipe decreases, the contact output is released by the return force of the micro switch and the deadweight of the diaphragm.
Model | KF-500 Standard Type |
Contact Capacity | AC250V 5A |
Allowable Temperature | -20~+70℃ |
Allowable Pressure | ATM |
Operating Water Level | 40 ± 10mm |
Breaking Water Level | 30 ± 10mm |
Color | Gold |
Process Connection | G1B |
Enclosure Rating | Equivalent to IP-54 |